|
Cement atious
Shake and Slate
A. ROOF DECK:
1. Roof deck may be spaced or solid
sheathing.
2. Fill in between existing spaced
sheathing boards is required as needed to meet nailing zone requirements.
IRCC recommends a complete fill in of spaced sheathing.
3. This material may not be applied
directly over rigid insulation board.
4. This material may not be used to
recover over any other roof..
B. UNDERLAYMENT / INTERLAYMENT:
1. All field felt shall be a
minimum 18” wide 30# felt interlayment installed to the desired field
exposure, not to exceed a nominal 10” exposure unless otherwise
specified by manufacturer. 102” exposure over 10 courses shall be
accepted as maximum tolerance.
3. All sheet metal valleys shall
have a 36” wide 30# felt underlayment unless otherwise specified by
manufacturer.
4. Slopes less than 4/12 require
additional underlayment. The IRCC recommends a mineral surfaced cap
sheet.
5. Application of cementatious
material on slopes under 3/12 should be over an impermeable membrane
where the shakes are installed for aesthetic purposes only.
C. FASTENERS:
1. Nails shall be EG type, box
nails, long enough to penetrate 3/4” into or through the sheathing
board.
2. Staples shall be galvanized
type, 7/16” crown minimum, long enough to penetrate 3/4” into or
through the sheathing board.
3. Shorter fasteners are
acceptable for use at overhangs and eaves to minimize penetration of the
visible underside.
4. Fasteners shall be located so
as to penetrate the underlying cementatious material and be covered by
the overlaying material. Two fasteners per tile are required.
D. STARTER COURSE:
1. Starter material should be
specified in the manufacturer’s instructions.
2. Starter should be fastened in the
same manner as field material.
E. FIELD TILES:
1. No felt shall be exposed
between the open keyways.
2. Keyway spacing shall be 5/8”
maximum.
3. Keyways in alternate courses
shall offset 1 1/2” minimum.
F. VALLEYS:
1. 28 gauge, 24” wide, W type
metal valley may be used. The cementatious material should overlap a
minimum of 6” on each flange.
G. CHIMNEY FLASHING:
1. May be reused if in serviceable
condition.
2. If counter flashing is
replaced, it may be fastened to the chimney with concrete nails and
sealed with a good exterior caulk.
H. ROOF JACKS AND PLUMBING VENTS:
1. May be reused if they are the
proper type and in serviceable condition.
2. Plumbing pipes may be sealed to
the flashing with flashing tape, rubber collar, or plastic cement.
3. Painting of flashing to blend
with the roofing is desirable but not required.
4. Exposed galvanized fasteners on
base flashing is acceptable.
I. MISCELLANEOUS FLASHINGS:
1. Edge metal is required to cover
exposed edges of plywood.
2. Painting of edge metal is not
required.
3. When flashing against a
vertical side wall:
a. New flashings may be installed
if feasible. If new flashings are installed on the exterior of the wall,
the flashing should be counter flashed with wood or metal sealed to the
wall with a good exterior caulk.
b. The old flashings may be reused
if they are the proper type and in serviceable condition. The flashings
should be lifted and installed with the new shingles.
J. HIP AND RIDGE:
1. Ridge should be installed with
one galvanized nail on each side penetrating into the sheathing at least
3/4”. Exposed nailing is acceptable.
2. Spacing of ridge shingles shall
match that of the field or manufacturer’s recommendations, whichever
is less.
K. BUILDING DEPARTMENT
INSPECTIONS:
1. In-progress inspections should
include spot checks of decking, plywood nailing, shingle application,
and flashing installation.
2. Final inspections should be
done from the ground to avoid damage to the cementatious material.
|